FCFQ-A Series
Cassette air conditioner with 360° uniform airflow sets the standard. Enabled with advanced KATAI Technology, it ensures Environment Friendly Operations and increased reliability.
Series Name: FCFQ50/71/90/100/125/140
Type: Inverter
Star Rating: 3
Salient Features
D III net compatible
Connection to a centralised control system is available without need for an optional adaptor. Available in Inverter Series only.
Drain pump mechanism
Steeper gradient realises more efficient condensate drainage. High-lift is especially useful for long lengths of drain piping.
Individual air flow control
Airflow direction can be individually adjusted for each air discharge outlet to deliver optimal air distribution.
KATAI Technology
K-Kosher Environment Friendly, A-Advance Technology, T-True Enhanced Life, A-Adequate Strength, I-Increased Reliability. Long life alloy for very aggressive Kosher environments.
Night quiet operation
The Automatic night quiet mode will initiate 8 hours after the peak temperature is reached in the daytime, and normal operation will resume 10 hours after that.
Silver ION antibacterial drain pan
A built-in anti-bacterial treatment that uses silver ion in the drain pan prevents the growth of bacteria, and mould that cause odours & clogging.
Specification
TECHNICAL SPECIFICATIONS 3 STAR INVERTER 3x3 CASSETTE AC
(FCFQ-SERIES WITH “KATAI” TECHNOLOGY)
Nominal Capacity | TR | 1.5 | 2 | 2.5 | 3 | 3.5 | 4 | |
Model Name | Outdoor Unit | RZFQ50AV16 | RZFQ71AV16 | RZFQ90AV16 | RZFQ100AV16 | RZFQ125AY16 | RZFQ140AY16 | |
Outdoor Unit | RZFQ50AV16 | RZFQ71AV16 | RZFQ90AV16 | RZFQ100AV16 | RZFQ125AY16 | RZFQ140AY16 | ||
Remote Control | Wireless(Optional) | Model No. | BRC91A152 | |||||
BRC7M632F-6 | ||||||||
Wired(Optional) | ------- | BRC1E63 | ||||||
Decorative Panel | Model Name | ------- | BYCQ125EAF6 (Non Sensi) | |||||
Performance | Rated Cooling Capacity | kW | 5.3 | 7.1 | 9 | 10.5 | 12.5 | 14 |
Min~Max Capacity | kW | 1.8~5.3 | 2.2~7.1 | 4.5~10.1 | 5.0~10.5 | 5.7~14.0 | 6.2~14.0/6.2~15.5 | |
Rated Power Input | kW | 1420 | 2350 | 2820 | 3430 | 4600/4450 | 5480/5250 | |
ISEER | Wh/Wh | 3.99 | 3.99 | 3.99 | 3.66 | 3.66/3.65 | 3.66/3.65 | |
Annual Power Consumption | kWh | 1022.39 | 1378.89 | 1745.56 | 2221.32 | 2652.48 | 2971.47 | |
BEE Star Rating | Star | 3-Star | ||||||
BEE Star Rating | DU (DB)℃ | 19~35 | ||||||
ODU (DB)℃ | 19~50 | |||||||
Power Supply | V/Hz/ph | 230V/50Hz/1ph | 400V/50Hz/3p | |||||
Refrigerant | ------- | R-32 | ||||||
Indoor Unit | Casing Siz | HxWxD (mm) | 256x840x840 | 400V/50Hz/3p | ||||
Casing Color | ------- | Galvanized Steel Coated | ||||||
Air Flow Rate (Hi) | cfm (H/HM/M/ML/L) | 812/741/653/565/476 | 1218/1095/972/848/707 | 1288/1165/1025/883/742 | ||||
Fan Speed | Nos | 5 | ||||||
Sound Pressure Leve | dBA (H/HM/M/ML/L) | 39/37/34/32/30 | 47/43.5/40/37/34.5 | 48/45/42/38/34.5 | ||||
Unit Weight | kg | 22 | 25 | |||||
Liquid Piping Dia. | mm | 6.35 | 6.35 | 9.52 | ||||
Gas Piping Dia. | mm | 12.7 | 15.8 | 15.88 | ||||
Max Total Pipe Length | mtr. | 20 | 30/50 | 30/50 | 30/50 | 30/50 | ||
Chargeless Pipe Length | mtr. | 10 | 10 | 10 | 10 | 10 | ||
Standard Pipe Length | mtr. | 7.5 | 7.5 | 7.5 | ||||
Max. Level Difference | mtr. | 15 | 20/30 | 20/30 | 20/30 | 20/30 | ||
Drain | mm | Dia 26 (Hole) | Dia 26 (Hole) | Dia 26 (Hole) | ||||
(Fresh White) | Size | HxWxD (mm) | 50x950x950 | |||||
Panel | Weight | kg | 5.5 | |||||
Outdoor Unit | ODU Shape | ------- | Side Discharge | |||||
ODU Qty. | Nos. | 1 | ||||||
Casing Size | HxWxD (mm) | 595x845x300 | 695x930x350 | 990x940x320 | ||||
Sound Pressure Level | dBA | 52 | 52 | 52 | 55/57 | 55/57 | ||
Compressor | Type/Qty-Nos. | Swing Compressor/1 | ||||||
HE Type | ------- | KATAI Technology | ||||||
Precharge & Service Valve | ------- | Yes | ||||||
nstallation Kit | ------- | No | ||||||
Weight(Approx) | kg | 32 | 40 | 48/44 | 48/44 | 68/62 | 68/62 |
Note :
- 1. Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; Outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5m (horizontal).
- 2. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
- 3. Star rating is applicable for single phase units upto a rated cooling capacity of 10,465 Watts as defined by Bureau of Energy Efficiency, Ministry of Power.
- 4. Star Rating is now applicable under Voluntary phase for Three phase units above a rated capacity of 10,465 watts as defined by Bureau of Energy Efficiency, Ministry of Power.