Enquire Now

VRV X

First launched in Japan in 1982, the daikin VRV X system has been embraced by the world markets for over three decades. Now, we at daikin introduce the next generation VRV X system to reinforce our industry leadership. The system now offers an enhanced line-up to meet an ever widening variety of needs, while improving energy savings, comfort and ease of installation.

The VRV X is the most advanced airconditioning system in the world and is ideal for large and small spaces.

VRT-Variable Refrigerant Temperature in Indoor Unit (IDU) and Outdoor Unit (ODU)

Product category:

Model: 
VRV X

Salient Features

Lower operation sound

Lower operation sound

Next-Gen Compressor & VRT Smart Control

Next-Gen Compressor & VRT Smart Control

Reliable & stable system

Reliable & stable system

Up to 60HP

Up to 60HP

Specification

VRV X (Cooling only)

 RXQ6-8-10-12ARYRXQ14-16ARY
MODELRXQ6ARY6/ARY-1RXQ8ARY6/ARY-1RXQ10ARY6/ARY-1RXQ12ARY6/ARY-1RXQ14ARY6/ARY-1RXQ16ARY6/ARY-1
Combination units------
Power supply3-phase, 380–415 V, 50 Hz
Cooling capacityBtu/h54,60076,40095,5001,14,0001,36,0001,54,000
kW1622.42833.54045
Capacity control%25~10020~10013~10012~10011~10010~100
Casing colourIvory white (5Y7.5/1)
CompressorTypeHermetically Sealed Scroll Type
No. of
compressor
 111112
Airflow ratem3/min119178191257
Dimensions (H×W×D)mm1,657X930X7651,657X1,240X765
Machine weightkg165175220260
Sound leveldB(A)565657596060
Operation
range
Cooling°CDB10 ~ 49
RefrigerantType R410A
Chargekg5.96.76.87.48.2
Piping
connections
Liquidmmø 9.5ø 12.7
Gasmmø 19.1ø 22.2ø 28.6

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

 RXQ-18-20ARYRXQ-22-24ARY
MODELRXQ18ARY6/ARY-1RXQ20ARY6/ARY-1RXQ22ARY6/ARY-1RXQ24ARY6/ARY-1
Combination units--RXQ10ARY6/ARY-1RXQ12ARY6
--RXQ12ARY6/ARY-1RXQ12ARY6
----
Power supply3-phase, 380–415 V, 50 Hz
Cooling capacityBtu/h1,71,0001,91,0002,10,0002,29,000
kW50.056.061.567.0
Capacity control%10~1007~1006~100
Casing colourIvory white (5Y7.5/1)
CompressorTypeHermetically Sealed Scroll Type
No. of
compressor
 221+11+1
Airflow ratem3/min257297178+191191+191
Dimensions (H×W×D)mm1,657X1,240X765(1,657X930X765)+(1,657X930X765)
Machine weightkg260285175+175
Sound leveldB(A)61656162
Operation
range
Cooling°CDB10 ~ 49
RefrigerantType R410A
Chargekg8.411.86.7+6.86.8+6.8
Piping
connections
Liquidmmø 15.9
Gasmmø 28.6ø 34.9

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

 RXQ-26-28-30-32ARYRXQ-34-36ARY
MODELRXQ26ARY6/ARY-1RXQ28ARY6/ARY-1RXQ30ARY6/ARY-1RXQ32ARY6/ARY-1RXQ34ARY6/ARY-1RXQ36ARY6/ARY-1
Combination unitsRXQ12ARY6/ARY-1RXQ12ARY6/ARY-1RXQ12ARY6/ARY-1RXQ14ARY6/ARY-1RXQ16ARY6/ARY-1RXQ18ARY6/ARY-1
RXQ14ARY6/ARY-1RXQ16ARY6/ARY-1RXQ18ARY6/ARY-1RXQ18ARY6/ARY-1RXQ18ARY6/ARY-1RXQ18ARY6/ARY-1
------
Power supply3-phase, 380–415 V, 50 Hz
Cooling capacityBtu/h2,47,0002,68,0002,85,0003,05,0003,24,0003,41,000
kW73.578.583.59095100
Capacity control%6~1005~1005~1005~1004~1005~100
Casing colourIvory white (5Y7.5/1)  
CompressorTypeHermetically Sealed Scroll Type
No. of
compressor
 1+11+21+21+22+22+2
Airflow ratem3/min191+257191+257191+257257+257257+257257+257
Dimensions (H×W×D)mm(1,657X930X765)+(1,657X1,240X765)(1,657X1,240X765)+(1,657X1,240X765)
Machine weightkg175+220175+260220+260260+260
Sound leveldB(A)6364
Operation
range
Cooling°CDB10 ~ 49
RefrigerantType R410A
Chargekg6.8+7.46.8+8.26.8+8.47.4+8.48.2+8.48.4+8.4
Piping
connections
Liquidmmø 19.1ø 19.1ø 19.1ø 19.1ø 19.1ø 19.1
Gasmmø 34.9ø 34.9ø 34.9ø 34.9ø 34.9ø 41.3

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

RXQ-38-40ARYRXQ-42-44ARYRXQ-46-48-50ARY
RXQ38ARY6/ARY-1RXQ40ARY6/ARY-1RXQ42ARY6/ARY-1RXQ44ARY6/ARY-1RXQ46ARY6/ARY-1RXQ48ARY6/ARY-1RXQ50ARY6/ARY-1
RXQ18ARY6/ARY-1RXQ20ARY6/ARY-1RXQ12ARY6/ARY-1RXQ12ARY6/ARY-1RXQ14ARY6/ARY-1RXQ14ARY6/ARY-1RXQ14ARY6/ARY-1
RXQ20ARY6/ARY-1RXQ20ARY6/ARY-1RXQ12ARY6/ARY-1RXQ12ARY6/ARY-1RXQ14ARY6/ARY-1RXQ16ARY6/ARY-1RXQ18ARY6/ARY-1
  RXQ18ARY6/ARY-1RXQ20ARY6/ARY-1RXQ18ARY6/ARY-1RXQ18ARY6/ARY-1RXQ18ARY6/ARY-1
3-phase, 380–415 V, 50 Hz
3,62,0003,82,0003,99,0004,20,0004,40,0004,57,0004,78,000
106112117123129134140
4~1003~1004~1003~100
Ivory white (5Y7.5/1)
Hermetically Sealed Scroll Type
2+21+1+21+2+2
257+297297+297191+191+257191+191+297257+257+257
(1,657X1,240X765)+
(1,657X1,240X765)
(1,657X930X765)+
(1,657X930X765)+
(1,657X1,240X765)
(1,657X1,240X765)+
(1,657X1,240X765)+
(1,657X1,240X765)
260+285285+285175+175+260175+175+285220+220+260220+260+260220+260+260
6668656765
10 ~ 49
R410A
8.4+11.811.8+11.86.8+6.8+8.46.8+6.8+11.87.4+7.4+11.87.4+8.2+8.47.4+8.4+8.4
ø 19.1
ø 41.3

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

 RXQ-52-54-56-58-60ARY
MODELRXQ52ARY6/ARY-1RXQ54ARY6/ARY-1RXQ56ARY6/ARY-1RXQ58ARY6/ARY-1RXQ60ARY6/ARY-1
Combination unitsRXQ16ARY6/ARY-1RXQ18ARY6/ARY-1RXQ18ARY6/ARY-1RXQ18ARY6/ARY-1RXQ20ARY6/ARY-1
RXQ18ARY6/ARY-1RXQ18ARY6/ARY-1RXQ18ARY6/ARY-1RXQ20ARY6/ARY-1RXQ20ARY6/ARY-1
RXQ18ARY6/ARY-1RXQ18ARY6/ARY-1RXQ20ARY6/ARY-1RXQ20ARY6/ARY-1RXQ20ARY6/ARY-1
Power supply3-phase, 380–415 V, 50 Hz
Cooling capacityBtu/h4,95,0005,12,0005,32,0005,53,0005,73,000
kW145150156162168
Capacity control%3~1002~100
Casing colourIvory white (5Y7.5/1)
CompressorTypeHermetically Sealed Scroll Type
No. of
compressor
 2+2+2
Airflow ratem3/min257+257+257257+297+297
Dimensions (H×W×D)mm(1,657X1,240X765 + 1,657X1,240X765 + 1,657X1,240X765)
Machine weightkg260+260+260260+260+285260+285+285285+285+285
Sound leveldB(A)6566686970
Operation
range
Cooling°CDB10 ~ 49
RefrigerantTypeR410A
Chargekg8.2+8.4+8.48.4+8.4+8.48.4+8.4+11.88.4+11.8+11.811.8+11.8+11.8
Piping
connections
Liquidmmø 19.1
Gasmmø 41.3

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

 RXQ-215ARYRXQ-430ARYRXQ-645ARY
MODELRXQ215ARY6BRXQ430ARY6BRXQ645ARY6B
Combination units RXQ215ARY6BRXQ215ARY6B
 RXQ215ARY6BRXYQ215TRY6B
  RXQ215ARY6B
Power supply3-phase, 380–415 V, 50 Hz
Cooling capacityBtu/h204,700409,400614,100
kW60120180
Power input (Cooling)kW19.739.459.1
C.O.P (Cooling) 3.053.053.05
Capacity Control%50-13050-13050-120
Casing ColourIvory white (5Y7.5/1)
CompressorTypeHermetically Sealed Scroll Type
No. of compressor246
Airflow ratem3/min297594891
Dimensions (H×W×D)mm1,657X1,240X765(1,657X1,240X765 + 1,657X1,240X765)(1,657X1,240X765 + 1,657X1,240X765 + 1,657X1,240X765)
Machine weightkg285285+285285+285+285
Sound leveldB(A)656870
Operation
range
Cooling°CDB10 ~ 49
RefrigerantTypeR410A
Chargekg11.811.8+11.811.8+11.8+11.8
Piping
connections
Liquidmmø 15.9 (Brazing)ø 19.1 (Brazing)ø 19.1 (Brazing)
Gasmmø 26.8 (Brazing)ø 41.3 (Brazing)ø 41.3 (Brazing)
 RXYQ6-8-10-12ARY
MODELRXYQ6ARY6RXYQ8ARY6RXYQ10ARY6RXYQ12ARY6
Combination units----
Power supply3-phase, 380–415 V, 50 Hz
Cooling capacityBtu/h54,60076,40095,5001,14,000
kW1622.42833.5
Heating capacityBtu/h61,40085,3001,07,0001,28,000
kW182531.537.5
Capacity Control%25-10025-10013-10012-100
Casing ColourIvory white (5Y7.5/1)
CompressorTypeHermetically Sealed Scroll Type
No. of compressor1
Airflow ratem3/min119178191
Dimensions (H×W×D)mm1,657X930X765
Machine weightkg180195
Sound leveldB(A)5657
Operation
range
Cooling°CDB-5 ~ 49
Heating°CDB-20 ~ 15.5
RefrigerantTypeR410A
Chargekg6.97.07.47.6
Piping
connections
Liquidmmø 9.5ø 12.7
Gasmmø 19.1ø 22.2ø 28.6

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0.
  • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

VRV X (Heat Pump)

 VRV-Heat-Pump-RXYQ14-16ARY
MODELRXYQ14ARY6RXYQ16ARY6
Combination units--
Power supply3-phase, 380–415 V, 50 Hz
Cooling capacityBtu/h1,36,0001,54,000
kW4045
Heating capacityBtu/h1,54,0001,71,000
kW4550
Capacity Control%11-10010-100
Casing ColourIvory white (5Y7.5/1)
CompressorTypeHermetically Sealed Scroll Type
No. of compressor2
Airflow ratem3/min257
Dimensions (H×W×D)mm1,657X1,240X765
Machine weightkg265
Sound leveldB(A)60
Operation
range
Cooling°CDB-5 ~ 49
Heating°CDB-20 ~ 15.5
RefrigerantTypeR410A
Chargekg9.19.3
Piping
connections
Liquidmmø 12.7
Gasmmø 28.6

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0.
  • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

 VRV-Heat-Pump-RXYQ-18-20ARYVRV-Heat-Pump-RXYQ-22-24ARY
MODELRXYQ18ARY6RXYQ20ARY6RXYQ22ARY6RXYQ24ARY6
Combination units--RXYQ10ARY6RXYQ12ARY6
  RXYQ12ARY6RXYQ12ARY6
Power supply3-phase, 380–415 V, 50 Hz
Cooling capacityBtu/h1,71,0001,91,0002,10,0002,29,000
kW50.056.061.567.0
Heating capacityBtu/h1,91,0002,15,0002,35,0002,56,000
kW56.063.069.075.0
Capacity Control%10-1007-1006-100
Casing ColourIvory white (5Y7.5/1)
CompressorTypeHermetically Sealed Scroll Type
No. of compressor21+1
Airflow ratem3/min257297178+191191+191
Dimensions (H×W×D)mm1,657X1,240X765(1,657X930X765)+(1,657X930X765)
Machine weightkg285305195+195
Sound leveldB(A)61656162
Operation
range
Cooling°CDB-5 ~ 49
Heating°CDB-20 ~ 15.5
RefrigerantTypeR410A
Chargekg11.87.4+7.67.6+7.6
Piping
connections
Liquidmmø 15.9
Gasmmø 28.6ø 34.9

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0.
  • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

 VRV-Heat-Pump-RXYQ-26-28-30-32ARYVRV-Heat-Pump-RXYQ-34-36ARY
MODELRXYQ26ARY6RXYQ28ARY6RXYQ30ARY6RXYQ32ARY6RXYQ34ARY6RXYQ36ARY6
Combination unitsRXYQ12ARY6RXYQ12ARY6RXYQ12ARY6RXYQ16ARY6RXYQ16ARY6RXYQ16ARY6
RXYQ14ARY6RXYQ16ARY6RXYQ18ARY6RXYQ16ARY6RXYQ18ARY6RXYQ20ARY6
Power supply3-phase, 380–415 V, 50 Hz
Cooling capacityBtu/h2,47,0002,68,0002,85,0003,05,0003,24,0003,45,000
kW73.578.583.590.095.0101.0
Heating capacityBtu/h2,99,0003,19,0003,41,0003,62,0003,86,000
kW82.587.593.5100.0106.0113.0
Capacity Control%5-1004-100
Casing ColourIvory white (5Y7.5/1)
CompressorTypeHermetically Sealed Scroll Type
No. of compressor1+22+2
Airflow ratem3/min191+257257+257257+297
Dimensions (H×W×D)mm(1,657X930X765)+(1,657X1,240X765)(1,657X1,240X765)+(1,657X1,240X765)
Machine weightkg195+265195+285265+265265+285265+305
Sound leveldB(A)636466
Operation rangeCooling°CDB-5 ~ 49
Heating°CDB-20 ~ 15.5
RefrigerantTypeR410A
Chargekg7.6+9.17.6+9.37.6+11.89.3+9.39.3+11.8
Piping
connections
Liquidmmø 19.1
Gasmmø 34.9ø 41.3

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0.
  • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

 VRV-Heat-Pump-RXYQ-38-40ARYVRV-Heat-Pump-RXYQ-42-44ARY
MODELRXYQ38ARY6RXYQ40ARY6RXYQ42ARY6RXYQ44ARY6
Combination unitsRXYQ18ARY6RXYQ20ARY6RXYQ12ARY6RXYQ12ARY6
RXYQ20ARY6RXYQ20ARY6RXYQ12ARY6RXYQ12ARY6
  RXYQ18ARY6RXYQ20ARY6
Power supply3-phase, 380–415 V, 50 Hz
Cooling capacityBtu/h3,62,0003,82,0003,99,0004,20,000
kW106.0112.0117.0123.0
Heating capacityBtu/h4,06,0004,30,0004,47,0004,71,000
kW119.0126.0131.0138.0
Capacity Control%4 - 1003 - 1004 - 1003 - 100
Casing ColourIvory white (5Y7.5/1)
CompressorTypeHermetically Sealed Scroll Type
No. of compressor2+21+1+2
Airflow ratem3/min257+297297+297191+191+257191+191+297
Dimensions (H×W×D)mm(1,657X1,240X765)+
(1,657X1,240X765)
(1,657X930X765)+
(1,657X930X765)+
(1,657X1,240X765)
Machine weightkg285+305305+305195+195+285200+200+325
Sound leveldB(A)66686567
Operation
range
Cooling°CDB-5 ~ 49
Heating°CDB-20 ~ 15.5
RefrigerantTypeR410A
Chargekg11.8+11.87.6+7.6+11.8
Piping
connections
Liquidmmø 19.1
Gasmmø 41.3

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0.
  • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

VRV-Heat-Pump-RXYQ-46-48-50ARYVRV-Heat-Pump-RXYQ-52-54-56-58-60ARY
RXYQ46ARY6RXYQ48ARY6RXYQ50ARY6RXYQ52ARY6RXYQ54ARY6RXYQ56ARY6RXYQ58ARY6RXYQ60ARY6
RXYQ14ARY6RXYQ16ARY6RXYQ16ARY6RXYQ16ARY6RXYQ18ARY6RXYQ18ARY6RXYQ18ARY6RXYQ20ARY6
RXYQ16ARY6RXYQ16ARY6RXYQ16ARY6RXYQ18ARY6RXYQ18ARY6RXYQ18ARY6RXYQ20ARY6RXYQ20ARY6
RXYQ16ARY6RXYQ16ARY6RXYQ18ARY6RXYQ18ARY6RXYQ18ARY6RXYQ20ARY6RXYQ20ARY6RXYQ20ARY6
3-phase, 380–415 V, 50 Hz
4,44,0004,61,0004,78,0004,95,0005,12,0005,32,0005,53,0005,73,000
130135140145.0150.0156.0162.0168
4,95,0005,12,0005,32,0005,53,0005,73,0005,97,0006,21,0006,45,000
145150156162.0168.0175.0182.0189
3 - 1002 - 100
Ivory white (5Y7.5/1)
Hermetically Sealed Scroll Type
2+2+2
257+257+257257+257+297257+257+257257+257+297257+297+297297+297+297
(1,657X1,240X765)+
(1,657X1,240X765)+
(1,657X1,240X765)
(1,657X1,240X765 + 1,657X1,240X765 + 1,657X1,240X765)
195+195+305265+265+265265+265+285265+285+285285+285+285285+285+305285+305+305305+305+305
6566686970
-5 ~ 49
-20 ~ 15.5
R410A
9.1+9.3+9.39.3+9.3+9.39.3+9.3+11.89.3+11.8+11.811.8+11.8+11.8
ø 19.1
ø 41.3

Note :

Specifications are based on the following conditions:

  • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0.
  • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
  • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

AS A PART OF CONTINOUS DEVELOPMENT AND UPGRADATION THE PRODUCT IMAGE/ACCESSORY/FEATURE/SPECIFICATION MAY BE DIFFERENT FROM ACTUAL PRODUCT AT THE TIME OF PURCHASE.

Customer Support Information: Give A Missed Call: @ 9210188999, Call Our Customer Contact Centre: 011-40319300or Write To Us at: customerservice@daikinindia.com
X