Enquire Now

Floor Standing Type, Duct Connection Type, R-410A, FVPGR Series (Cooling Only)

We have entered an era in which being recognised as an environmentally responsible corporate citizen has taken utmost importance. Even when selecting air conditioners, a new model featuring HFC R-410A refrigerant could be the perfect step in promoting your corporate image.

Power Supply:

Product category:

Model: 
FVPGR10

Available in (kW):

Specification

Floor Standing Type (Cooling Only) - Duct Connection Type

r410a
Model name 8.3 TR10 TR13.3 TR15.0 TR16.7 TR
Indoor unitFVPGR10NY1FVPGR13NY1FVPGR15NY1FVPGR18NY1FVPGR20NY1
Outdoor unitRUR10NY1RUR13NY1RUR15NY1RUR18NY1RUR20NY1
Power supply 380-415 V, 50 Hz, 3 Phase, 4 Wires
Cooling capacity 1,3kW29.335.246.952.858.6
Btu/h100000120000160000180000200000
kcal/h2520030200403004540050400
Running currentA19.224.32934.640.4
Power consumption 1kW11.414.917.821.224.8
Starting currentA129.5118130.3143.4146.3
Power factor%85.788.588.688.488.6
Indoor unit
ColourIvory White
Air Flow rate (H)m3/min80120120162162
cfm28304240424057205720
FanDrive Belt Drive
Ext. Static Pressure(mmH2O)15
Sound level 2dBA6162626363
Dimensions (HxWxD)mm1,740x1,170x5101,870x1,170x7201,870x1,170x7201,870x1,470x7201,870x1,470x720
Machine weightkg150180180240240
Operation range°CWB14 to 25
Outdoor unit
ColourIvory White
CompressorType Hermetically sealed scroll type 
Motor outputkW95.0+5.06.7+6.77.5+7.59.0+9.0
Refrigerant oilModel Refer to the name plate of compressor 
ChargeL3.356.56.56.5
Refrigerant charge (R-410A)kg6.0 (Charged for 7.5 m)4.5 (Charged for 7.5 m)8.0 (Charged for 7.5 m)8.0 (Charged for 7.5 m)8.0 (Charged for 7.5 m)
Sound level 2380VdBA6161626363
415VdBA6262636464
Dimensions (HxWxD)mm1,680x930x7651,680x1,240x7651,680x1,240x7651,680x1,240x7651,680x1,240x765
Machine weightkg206243319322329
Operation range°CDB21 to 46
Refrigerant Piping
Indoor UnitLiquidmmØ12.7 (Brazing)Ø12.7 (Brazing)15.9 (Brazing)15.9 (Brazing)15.9 (Brazing)
GasmmØ28.6 (Brazing)Ø28.6 (Brazing)34.9 (Brazing)34.9 (Brazing)34.9 (Brazing)
DrainmmPS 1B Internal thread
Outdoor UnitLiquidmmØ12.7 (Flare)Ø12.7 (Flare)Ø15.9 (Flare)Ø15.9 (Flare)Ø15.9 (Flare)
GasmmØ28.6 (Brazing)Ø28.6 (Brazing)Ø34.9 (Brazing)Ø34.9 (Brazing)Ø34.9 (Brazing)
Drainmm-
Max. interunit piping lengthm50 (equivalent length 70 m)
Max. installation level differencem30

Note :

  • Rated cooling capacities are based on the following conditions: Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
  • Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
  • Capacity includes indoor fan motor heat.

AS A PART OF CONTINOUS DEVELOPMENT AND UPGRADATION THE PRODUCT IMAGE/ACCESSORY/FEATURE/SPECIFICATION MAY BE DIFFERENT FROM ACTUAL PRODUCT AT THE TIME OF PURCHASE.

Customer Support Information: Give A Missed Call: @ 9210188999, Call Our Customer Contact Centre: 011-40319300or Write To Us at: customerservice@daikinindia.com
X