FCVFQ Series Cooling Only

Cassette air conditioner with 360° uniform airflow sets the standard. It’s all around air flow uplifts the comfort level with uniform cooling and features like Silver ION Antibacterial Drain Fan ensures clean & fresh air.
Series Name: FCVFQ50/71/90/100/125/140
Type: Inverter
Star Rating: 3
Salient Features
D III net compatible

Connection to a centralised control system is available without need for an optional adaptor. Available in Inverter Series only.
Drain pump mechanism

Steeper gradient realises more efficient condensate drainage. High-lift is especially useful for long lengths of drain piping.
Individual air flow control

Airflow direction can be individually adjusted for each air discharge outlet to deliver optimal air distribution.
Night quiet operation

The Automatic night quiet mode will initiate 8 hours after the peak temperature is reached in the daytime, and normal operation will resume 10 hours after that.
Swing pattern selection

You can freely set air discharge settings by remote controller. One can choose from Standard setting, Draft prevention setting and Ceiling soiling prevention setting.
Silver ION antibacterial drain pan

A built-in anti-bacterial treatment that uses silver ion in the drain pan prevents the growth of bacteria, and mould that cause odours & clogging.
Auto restart

If there is a power outage while the equipment is operating, operations will restart in the same mode as before the power cut when electricity is restored.
Energy consumption monitoring

Past power consumption is displayed for the current and previous days as well as in weekly and yearly intervals.
Specification
Round Flow Cassette Cooling Only - 3 Star Inverter R-32 (FCVFQ-Series)

Nominal Capacity | TR | 1.5 | 2 | 2.5 | 3 | 3.5 | 4 | |
Model | Indoor unit | FCVFQ50AV16 | FCVFQ71AV16 | FCVFQ90AV16 | FCVFQ100AV16 | FCVFQ125AV16 | FCVFQ140AV16 | |
Outdoor unit | RZVFQ50AV16 | RZVFQ71AV16 | RZVFQ90AV16 | RZVFQ100AV16 | RZVFQ125AY16 | RZVFQ140AY16 | ||
Remote | Wireless | Optional | BRC91A152 | |||||
Signal Receiver Unit - Model Number | BRC7M632F-6 | |||||||
Wired | Optional | BRC1E63 | ||||||
Panel Code | With Sensing | BYCQ125EAF6 | ||||||
Power supply | V/Hz/ph | 230V/50Hz/1ph | 400V/50Hz/3ph | |||||
Cooling capacity -Rated (min ~max) | kW | 5.3 (1.8~5.3) | 7.1 (2.2~7.1) | 9 (4.5~9) | 10.5 (5.0~10.5) | 12.5 (5.7~12.5) | 14 (6.2~14.0) | |
Power consumption | Cooling-Rated | kW | 1.42 | 2.35 | 2.82 | 3.43 | 4.45 | 5.25 |
Annual Power Consumption | kWh | 1022.39 | 1378.89 | 1745.56 | 2221.32 | 2652.48 | 2971.47 | |
ISEER / Stars | Wh/Wh | 3.99/3 | 3.99/3 | 3.99/3 | 3.66/2 | 3.65/3 | 3.65/3 | |
Indoor unit | ||||||||
Colour | Galvanized Steel Plate | |||||||
Airflow rate (H/HM/M/ML/L) | m3/min | 23 / 21 / 18.5 / 16 / 13 | 34.5 / 31 / 27.5 / 24 / 20 | 36.5/33/29/25/21 | ||||
cfm | 812/741/653/565/476 | 1218/1095/971/848/706 | 1288/1165/1025/883/742 | |||||
Sound level (H/HM/M/ML/L) | dB(A) | 39/37/34/32/30 | 46/43.5/40/37/34.5 | 47/44/42/39/35.5 | ||||
Dimensions (HXWXD) | Unit | mm | 256x840x840 | 298x840x840 | ||||
Panel | mm | 50x950x950 | ||||||
Machine weight | Unit | kg | 22 | 25 | ||||
Panel | kg | 5.5 | ||||||
Drain | mm | VP25 (I.D. ⌀ 25, O.D. ⌀ 32) | ||||||
Outdoor unit | ||||||||
Colour | Ivory White | |||||||
Compressor | Type | Hermetically Sealed Swing Type | ||||||
Motor output | kW | 0.92 | 1.2 | 1.6 | 2.4 | |||
Refrigerant | R32 | |||||||
Refrigerant charge | kg | 0.98 | 1.04 | 1.3 | 2.1 | |||
Sound level | Cooling | dB(A) | 54 | 52 | 55 | |||
Dimensions (HXWXD) | mm | 595x845x300 | 695x930x350 | 990x940x320 | ||||
Machine weight | kg | 31 | 39 | 48.5 | 66 | |||
Certified operation range | °CDB | 19 ~ 50 | ||||||
Piping connections | Liquid (Flare) | mm | 6.35 | 9.52 | ||||
Gas (Flare) | mm | 12.7 | 15.88 | |||||
Max. interunit piping length | m | 20 | 30 | |||||
Max. installation level difference | m | 20 | 30 |
Note :
- 1. Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; Outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5m (horizontal).
- 2. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
- 3. Star rating is applicable for single phase units upto a rated cooling capacity of 10,465 Watts as defined by Bureau of Energy Efficiency, Ministry of Power
- 4. Star Rating is now applicable under Voluntary phase for Three phase units above a rated capacity of 10,465 watts as defined by Bureau of Energy Efficiency, Ministry of Power.