Skip to main content
Enquire Now

FDMA Series​

Cooling & Heating​

FDMA Series​

FDMA Series​ | Daikin

The compact, and elegant design Ceiling Concealed Indoor Unit of the FDMF-Q Series are the perfect answers for the air-conditioners requirements of building with minimum Ceiling Installation space and wide-ranging external static pressure, energy saving efficiency has been improved, thereby reducing electricity consumption.​

Product Category

Available in (kW):

Specification

Ductable Cooling & Heating Inverter R-32 (FDMA-Series)

r32 icon
Nominal Capcity1.523.54
Model
Name
Indoor unitFDMA50AV16FDMA71AV16FDMA125AV16FDMA140AV16
Outdoor unitRZA50AV16RZA71AV16RZA125AV16RZA140AV16
RemoteWireless OptionalBRC4C65BRC4C65BRC4C65BRC4C65
WiredOptionalBRC1E63BRC1E63BRC1E63BRC1E63
Panel CodeWith Sensing-
Power supply1 Phase, 230V, 50Hz1 Phase, 230V, 50Hz1 Phase, 230V, 50Hz1 Phase, 230V, 50Hz
Cooling capacity -Rated (min ~max)kW5.00(1.80~5.28)7.10 (2.50 ~ 8.02)12.5 (4.03 ~ 13.3)14.0 (5.01~14.00)
Heating capacity -Rated (min ~max)kW5.007.113.515.0
Power consumptionCooling-RatedkW1.661.954.655.95
Annual Power ConsumptionkWh----
ISEER / StarsWh/Wh----
Indoor unitColour-
Airflow rate ((H/HM/M/ML/L)m3/min18/15/12.523/19.5/1640/34/2840/34/28
cfm636/530/441812/687/5651412/1200/9891412/1200/989
Sound level  (H/HM/M/ML/L)dB(A)38/35/3343/38/3443/40/3643/40/36
External Static PressurePaRATED 50 (50-150)*
Dimensions (HXWXD)Unitmm300×1000×700300×1000×700300×1400×700300×1400×700
Panelmm-
Machine WeightUnitkg34344545
Panelkg-
DrainmmØ18 (Hole)Ø26 (Hole)Ø26 (Hole)Ø26 (Hole)
Outdoor unitColourIvory White
CompressorType HERMETICALLY SEALED SWING TYPE
Motor outputkW0.921.13.33.3
Refrigerant  R32
Refrigerant charge kg0.721.22.92.9
Sound levelCoolingdB(A)52525353
Dimensions (HXWXD)mm595X845X300930×695×418990×940×320990×940×320
Machine weightkg28477878
Certified operation range°CDB-10 Deg C to 52 Deg C-15 Deg C to 52 Deg C
Piping
connections
Liquid (Flare)mmØ6.4 (Flare)Ø6.4 (Flare)Ø9.5 (Flare)Ø9.5 (Flare)
Gas (Flare)mmØ12.7 (Flare)Ø15.9 (Flare)Ø15.9 (Flare)Ø15.9 (Flare)
Max. interunit piping lengthm20305050
Max. installation level differencem16203030

Note :

  • Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; Outdoor temp. 35°CDB. Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB; Outdoor temp., 7°CDB, 6°CWB. All unit are being tested and comply to ISO 5151 (Non-ducted unit)

Customer Support Information: WhatsApp us your query @ 9871409300. Call Our Customer Contact Centre: 011-40319300 / 1860 180 3900 or Write To Us at customerservice@daikinindia.com

X