FDMA Series
The compact, and elegant design Ceiling Concealed Indoor Unit of the FDMF-Q Series are the perfect answers for the air-conditioners requirements of building with minimum Ceiling Installation space and wide-ranging external static pressure, energy saving efficiency has been improved, thereby reducing electricity consumption.
Specification
Ductable Cooling & Heating Inverter R-32 (FDMA-Series)
| Nominal Capcity | 1.5 | 2 | 3.5 | 4 | |||
| Model Name | Indoor unit | FDMA50AV16 | FDMA71AV16 | FDMA125AV16 | FDMA140AV16 | ||
| Outdoor unit | RZA50AV16 | RZA71AV16 | RZA125AV16 | RZA140AV16 | |||
| Remote | Wireless | Optional | BRC4C65 | BRC4C65 | BRC4C65 | BRC4C65 | |
| Wired | Optional | BRC1E63 | BRC1E63 | BRC1E63 | BRC1E63 | ||
| Panel Code | With Sensing | - | |||||
| Power supply | 1 Phase, 230V, 50Hz | 1 Phase, 230V, 50Hz | 1 Phase, 230V, 50Hz | 1 Phase, 230V, 50Hz | |||
| Cooling capacity -Rated (min ~max) | kW | 5.00(1.80~5.28) | 7.10 (2.50 ~ 8.02) | 12.5 (4.03 ~ 13.3) | 14.0 (5.01~14.00) | ||
| Heating capacity -Rated (min ~max) | kW | 5.00 | 7.1 | 13.5 | 15.0 | ||
| Power consumption | Cooling-Rated | kW | 1.66 | 1.95 | 4.65 | 5.95 | |
| Annual Power Consumption | kWh | - | - | - | - | ||
| ISEER / Stars | Wh/Wh | - | - | - | - | ||
| Indoor unit | Colour | - | |||||
| Airflow rate ((H/HM/M/ML/L) | m3/min | 18/15/12.5 | 23/19.5/16 | 40/34/28 | 40/34/28 | ||
| cfm | 636/530/441 | 812/687/565 | 1412/1200/989 | 1412/1200/989 | |||
| Sound level (H/HM/M/ML/L) | dB(A) | 38/35/33 | 43/38/34 | 43/40/36 | 43/40/36 | ||
| External Static Pressure | Pa | RATED 50 (50-150)* | |||||
| Dimensions (HXWXD) | Unit | mm | 300×1000×700 | 300×1000×700 | 300×1400×700 | 300×1400×700 | |
| Panel | mm | - | |||||
| Machine Weight | Unit | kg | 34 | 34 | 45 | 45 | |
| Panel | kg | - | |||||
| Drain | mm | Ø18 (Hole) | Ø26 (Hole) | Ø26 (Hole) | Ø26 (Hole) | ||
| Outdoor unit | Colour | Ivory White | |||||
| Compressor | Type | HERMETICALLY SEALED SWING TYPE | |||||
| Motor output | kW | 0.92 | 1.1 | 3.3 | 3.3 | ||
| Refrigerant | R32 | ||||||
| Refrigerant charge | kg | 0.72 | 1.2 | 2.9 | 2.9 | ||
| Sound level | Cooling | dB(A) | 52 | 52 | 53 | 53 | |
| Dimensions (HXWXD) | mm | 595X845X300 | 930×695×418 | 990×940×320 | 990×940×320 | ||
| Machine weight | kg | 28 | 47 | 78 | 78 | ||
| Certified operation range | °CDB | -10 Deg C to 52 Deg C | -15 Deg C to 52 Deg C | ||||
| Piping connections | Liquid (Flare) | mm | Ø6.4 (Flare) | Ø6.4 (Flare) | Ø9.5 (Flare) | Ø9.5 (Flare) | |
| Gas (Flare) | mm | Ø12.7 (Flare) | Ø15.9 (Flare) | Ø15.9 (Flare) | Ø15.9 (Flare) | ||
| Max. interunit piping length | m | 20 | 30 | 50 | 50 | ||
| Max. installation level difference | m | 16 | 20 | 30 | 30 | ||
Note :
- Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; Outdoor temp. 35°CDB. Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB; Outdoor temp., 7°CDB, 6°CWB. All unit are being tested and comply to ISO 5151 (Non-ducted unit)